  Useful Electrical Formulae
  Common Conversional Factors

 

 
Useful Electrical Formulae for Determining Amperes, Horsepower, Kilowatts and Kilovolts Amperes
To find Direct Current Alternative Current
Single Phase Three Phase
Amperes when Horsepower is known HP x 746
E x Eff
HP x 746
E x Eff x PF
HP x 746
1.73 x E xEff x PF
Amperes when Kilowatts is known KW x 1000
E
KW x 1000
E x PF
KW x 1000
1.73 x E x PF
Amperes when Kilovolt is known KVA x 1000
E
KVA x 1000
E
KVA x 1000
1.73 x E
Kilowatts I x E
1000
I x E x PF
1000
I x E x 1.73 x PF
1000
Kilovolt Amperes I x E
1000
I x E
1000
I x E x 1.73
1000
Horsepower(output) I x E x Eff
746
I x E x Eff x PF
746
I x E x 1.73 x Eff x PF
746

 

Notes :

I = Amperes
E = Phase to phase volts
Eff = Efficiency expressed as decimal (95% = 0.95)
PF = Power factor expresses as decimal (85% = 0.85)
KW = Kilowatts
KVA = Kilovolt Amperes
HP = Horsepower