CPRI Test Report
CMRI Test Report
KEMA Test Report
BVIS Test Report
ERDA Test Report
RITES Test Report


CPRI TEST REPORT
  Cable Type Test Details Test Report No. Customer
  3X70+1X35+1X10 SQ.MM. 1.9/3.3 kV CABLE AS PER IS–1026/1984 CR/HV BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR

CC–3114
 DT.24.05.90

 
  3X185 11 kV(E). A2XCEFY WITH ONE INDOOR
& ONE OUTDOOR TERMINATION AND ONE JOINT
PD/HV BEFORE AND AFTER HEATING CYCLE. SAMPLE FAILED IN PD

CC–3195
 DT.08.10.90

 
  A2XCEWY 3X150 SQ.MM. 6.6 kV (UE) CR/PD/POWER FACTOR/VR/HV BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR CC-3342
DT.19.09.91
&
CC 3341
DT.19.06.91
 
  A2XSEH 3X185 (AC)/25 (CU) 6/10 kV (E) HV/CR/PD BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR CC–3343
DT.27.06.91
 
  2XCY 1X400 SQ.MM. 76/132 kV TYPE TEST AS PER IEC 840 –1988 (INCLUDING IMPULSE TEST WITH PRINT OUT) CC–3365
DT.11.07.91
 
  2XCY 1X400 SQ.MM. 76/132 kV HV TEST ON SAMPLE 220 kV AC FOR 4 HOURS CC–3366
DT.11.07.91
 
  A2XCYWAY 1X400 SQ.MM. 19/33 kV (E) ROUTINE TESTS BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR AND SHORT CKT TEST THROUGH ARMOUR AND SCREEN CC–3368 a
&b
DT.22.07.91
 
  APLYSTS 3X120 SQ.MM. 6.35/11 kV (E) CR/HR BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR CC–3423
DT.30.09.91
 
* A2XCEFY 3X240 SQ.MM.6.35/11 kV (E) ELECTRICAL TYPE TEST. T.S.
& ELONG. HOT SET ON INSULATION AND ROUTINE TESTS BEFORE
& AFTER SHORT CKT TEST ON CONDUCTOR
CC–3449
DT.11.11.91
KSEB
  APLYSTS 3X185 SQ.MM. 6.35/11 kV(E) TYPE AND OPTIONAL TESTS AS PER IS:692/1973 CC–3469 a
DT.01.01.92
& CC 3469 b
DT.02.01.92
PSEB
  APLYSTS 3X240 SQ.MM. 19/33 kV (E) ROUTINE TESTS BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR. CC–3484
DT.02.01.92
 
  A2XC2YWAY 1X240 SQ.MM. 38/66 kV (E) TYPE TESTS AS PER IEC–840/1988 (IMPULSE TEST WITH PRINT OUT) CC–3675 (a)
DT.02.09.92
GEB
* A2XCEFY 3X300 SQ.MM. 12.7/22 kV (E) ROUTINE TESTS BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR CC–3816
DT.11.02.93
MSEB
* 2XCEFY 3X120 SQ.MM. 6.35/11 kV (E) O.S., T.S. AND ELONG. BEFORE AND AFTER U.V. EXPOSURE (DIN 53387) CC–3851
DT.19.03.93
TCE/
BANGLORE
* YFAY 1X120 SQ.MM. 0.65/1.1 kV O.S., T.S. AND ELONG. BEFORE AND AFTER U.V. EXPOSURE (DIN 53387) CC–3860 (B)
DT.02.04.93
TCE/
BANGLORE
* YFY 3X50 SQ.MM. 0.65/1.1 kV O.S., T.S. AND ELONG. BEFORE AND AFTER U.V. EXPOSURE (DIN 53387) CC–3860 (A)
DT.02.04.93
TCE/
BANGLORE
* A2XCEFY 3X240 SQ.MM. 6.35/11 kV (E) ROUTINE TESTS BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR CC–3861
DT.06.06.93
NTPC/
DELHI
  A2XCEFY 3X185 SQ.MM. 6.35/11 kV (E) ROUTINE TESTS BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR (TAN DELTA AS A FUNCTION OF VOLTAGE AND CAPACITANCE) CC–3988 (A+B)
DT.26.07.93
UPSEB
* AWXCEFY 3X240 SQ.MM. 6.35/11 kV (E) ELECTRICAL TYPE TEST AND ACCEPTANCE TESTS AND SHORT CKT TEST ON CONDUCTOR. ROUTINE TEST BEFORE AND AFTER SHORT CKT TEST 3410 (A)
DT.13.09.91
KSEB
* A2CEFAY 1X500 SQ.MM. 110 kV (E) (POLY AL TAPE) 1) ROUTINE TESTS BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR. 2) LONGITUDINAL WATER TIGHTNESS TEST. 3) INDUCED VOLTAGE TEST. CC–4603
DT.12.06.95
KSEB
  A2XCEFY 3X400 SQ.MM. 19/33 kV CR.HV. PD BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR CC–4829
DT.22.12.95
MSEB
  2XLyL 1X400 SQ.MM 64/110 kV SHORT TIME CURRENT TEST ON LEAD SHEATH SC/95/273/A
DT.25.01.96
 
* 2XAY 1X630 SQ.MM. 38/66 kV (E) SHORT CKT TEST ON CORRUGATED ALUMINIUM SHEATH SC–9811 A
DT.27.03.98
KEB
  ' * ' = Witnessed by Client      
  STJ = Straight Through Joint      
  ET = End Termination      
  CMRI TEST REPORT                                                             Back To Top
         
  Cable Type Test Details Test Report No. Customer
  7M 3X25+1X25+1X16 - 640/1100 V AS PER NCB 188/1978 + AMD. 5 E/T/7/2000
DT 23/5/2000
DONE AT CMRI
  4X50 RR 1.1 kV AS PER IS 9968 PART I/1988 E/T/20/91
DT 7/11/91
DONE AT CMRI
  RCgCR 3X120+3X70/3 6.35 kV AS PER IS 9968 PART II/1981 E/T/21/91
DT 7/11/91
DONE AT CMRI
  RCgCESR 3X70+3X35/3 6.6 kV (UE) AS PER IS 9968 PART II/1981 E/T/7/92
DT 12/3/92
DONE AT CMRI
  YWY 4X2.5 MM2 650/1100V MINIUM AS PER IS I554 PART I/1988 E/T/13/99
DT 25/10/97
 
  KEMA TEST REPORT                                                             Back To Top
  Cable Type Test Details Test Report No. Customer
  2XCY1x630 RM/V 127/220 kV AS PER IEC-840/1988 22192.00-HSC.
93-1078
DT 18/5/1993
KEMA, NETHE-
-RLAND
  BVIS TEST REPORT
  Cable Type Test Details Test Report No. Witnessed
by
  A2XCEWY 3x95 6.35/11 kV AS PER BS-6622/1991 8/8/97 BVIS
  APLyYWY 4x95 600/1100 V AS PER BS-6480/1988 2/23/98 BVIS
  A2XFY 2x25 0.6/1 kV AS PER IEC 502/1994 8/8/97 BVIS
  2XCYWaY 1X500 18/30 kV AS PER IEC 502/1994 9/7/98 BVIS
  A2XCEWY 3x95 6/10 kV AS PER IEC 502/1994 8/8/97 BVIS
  ERDA TEST REPORT                                                             Back To Top
  Cable Type Test Details Test Report No. Customer
  AYFY 3X400 1.1 kV Tests for UV Exposure as per ASTM-4-53-1984 on outer sheath 1.02/11/1395
DT 28/3/95
 
  A2XCEFY 11 kV Tests for UV Exposure as per ASTM-4-53-1984 on outer sheath 1.02/11/1287
DT 7/4/93
 
  A2XCEFY 3X185 11 kV Tests for UV Exposure as per ASTM-4-53-1984 on outer sheath 1.02/11/951
DT 3/11/93
 
  RITES TEST REPORT                                                             Back To Top
  Cable Type Test Details Test Report No. Witnessed
by
  RR 1X25 -   1500 V E14/01 PART II REV II-1993 5/19/00 RITES
  RR 19X3 -     750 V E14/01 PART I REV II-1993 3/28/00 RITES
  RR 1X120 - 1500 V E14/01 PART II REV II-1993 3/28/00 RITES
  RR 1X270 - 1500 V E14/01 PART II REV II-1993 3/28/00 RITES
  RR 1X225 - 1500 V E14/01 PART II REV II-1993 2/23/96 RITES
  RR 1X2.5 -   750 V E14/01 PART I REV II-1993 2/23/96 RITES
  RR 1X120 - 1500 V E14/01 PART II REV II-1993 2/17/95 RITES

Back To Top

 
 
 