Cable
Type
|
Test
Details
|
Test
Report No. |
Customer
|
|
|
3X70+1X35+1X10
SQ.MM. 1.9/3.3 kV CABLE AS PER IS–1026/1984
|
CR/HV BEFORE
AND AFTER SHORT CKT TEST ON CONDUCTOR |
CC–3114
DT.24.05.90
|
|
|
|
3X185
11 kV(E). A2XCEFY WITH ONE INDOOR
& ONE OUTDOOR TERMINATION AND ONE JOINT
|
PD/HV BEFORE
AND AFTER HEATING CYCLE. SAMPLE FAILED IN PD
|
CC–3195
DT.08.10.90
|
|
|
|
A2XCEWY
3X150 SQ.MM. 6.6 kV (UE) |
CR/PD/POWER FACTOR/VR/HV
BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR
|
CC-3342
DT.19.09.91
&
CC 3341
DT.19.06.91 |
|
|
|
A2XSEH
3X185 (AC)/25 (CU) 6/10 kV (E) |
HV/CR/PD BEFORE
AND AFTER SHORT CKT TEST ON CONDUCTOR |
CC–3343
DT.27.06.91 |
|
|
|
2XCY
1X400 SQ.MM. 76/132 kV |
TYPE TEST AS
PER IEC 840 –1988 (INCLUDING IMPULSE TEST WITH PRINT
OUT) |
CC–3365
DT.11.07.91 |
|
|
|
2XCY
1X400 SQ.MM. 76/132 kV |
HV TEST ON SAMPLE
220 kV AC FOR 4 HOURS |
CC–3366
DT.11.07.91 |
|
|
|
A2XCYWAY
1X400 SQ.MM. 19/33 kV (E) |
ROUTINE TESTS
BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR AND
SHORT CKT TEST THROUGH ARMOUR AND SCREEN
|
CC–3368 a
&b
DT.22.07.91 |
|
|
|
APLYSTS
3X120 SQ.MM. 6.35/11 kV (E) |
CR/HR BEFORE
AND AFTER SHORT CKT TEST ON CONDUCTOR |
CC–3423
DT.30.09.91 |
|
| *
|
A2XCEFY
3X240 SQ.MM.6.35/11 kV (E) |
ELECTRICAL TYPE
TEST. T.S.
& ELONG. HOT SET ON INSULATION AND ROUTINE TESTS
BEFORE
& AFTER SHORT CKT TEST ON CONDUCTOR
|
CC–3449
DT.11.11.91 |
KSEB |
|
|
APLYSTS
3X185 SQ.MM. 6.35/11 kV(E) |
TYPE AND OPTIONAL
TESTS AS PER IS:692/1973 |
CC–3469 a
DT.01.01.92
& CC 3469 b
DT.02.01.92 |
PSEB |
|
|
APLYSTS
3X240 SQ.MM. 19/33 kV (E) |
ROUTINE TESTS
BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR.
|
CC–3484
DT.02.01.92 |
|
|
|
A2XC2YWAY
1X240 SQ.MM. 38/66 kV (E) |
TYPE TESTS AS
PER IEC–840/1988 (IMPULSE TEST WITH PRINT OUT)
|
CC–3675 (a)
DT.02.09.92 |
GEB |
| *
|
A2XCEFY
3X300 SQ.MM. 12.7/22 kV (E) |
ROUTINE TESTS
BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR
|
CC–3816
DT.11.02.93 |
MSEB |
| *
|
2XCEFY
3X120 SQ.MM. 6.35/11 kV (E) |
O.S., T.S. AND
ELONG. BEFORE AND AFTER U.V. EXPOSURE (DIN 53387)
|
CC–3851
DT.19.03.93 |
TCE/
BANGLORE |
| *
|
YFAY
1X120 SQ.MM. 0.65/1.1 kV |
O.S., T.S. AND
ELONG. BEFORE AND AFTER U.V. EXPOSURE (DIN 53387)
|
CC–3860 (B)
DT.02.04.93 |
TCE/
BANGLORE |
| *
|
YFY
3X50 SQ.MM. 0.65/1.1 kV |
O.S., T.S. AND
ELONG. BEFORE AND AFTER U.V. EXPOSURE (DIN 53387)
|
CC–3860 (A)
DT.02.04.93 |
TCE/
BANGLORE |
| *
|
A2XCEFY
3X240 SQ.MM. 6.35/11 kV (E) |
ROUTINE TESTS
BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR
|
CC–3861
DT.06.06.93 |
NTPC/
DELHI |
|
|
A2XCEFY
3X185 SQ.MM. 6.35/11 kV (E) |
ROUTINE TESTS
BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR (TAN
DELTA AS A FUNCTION OF VOLTAGE AND CAPACITANCE)
|
CC–3988 (A+B)
DT.26.07.93 |
UPSEB
|
| *
|
AWXCEFY
3X240 SQ.MM. 6.35/11 kV (E) |
ELECTRICAL TYPE
TEST AND ACCEPTANCE TESTS AND SHORT CKT TEST ON
CONDUCTOR. ROUTINE TEST BEFORE AND AFTER SHORT CKT
TEST |
3410 (A)
DT.13.09.91 |
KSEB |
| *
|
A2CEFAY
1X500 SQ.MM. 110 kV (E) (POLY AL TAPE) |
1) ROUTINE TESTS
BEFORE AND AFTER SHORT CKT TEST ON CONDUCTOR. 2)
LONGITUDINAL WATER TIGHTNESS TEST. 3) INDUCED VOLTAGE
TEST. |
CC–4603
DT.12.06.95 |
KSEB |
|
|
A2XCEFY
3X400 SQ.MM. 19/33 kV |
CR.HV. PD BEFORE
AND AFTER SHORT CKT TEST ON CONDUCTOR |
CC–4829
DT.22.12.95 |
MSEB |
|
|
2XLyL
1X400 SQ.MM 64/110 kV |
SHORT TIME CURRENT
TEST ON LEAD SHEATH |
SC/95/273/A
DT.25.01.96 |
|
| *
|
2XAY
1X630 SQ.MM. 38/66 kV (E) |
SHORT CKT TEST
ON CORRUGATED ALUMINIUM SHEATH |
SC–9811 A
DT.27.03.98 |
KEB |
|
|
'
* ' = Witnessed by Client |
|
|
|
|
|
STJ
= Straight Through Joint |
|
|
|
|
|
ET
= End Termination |
|
|
|
|
|
CMRI
TEST
REPORT
Back
To Top |
|
|
|
|
|
|
|
|
Cable
Type |
Test
Details
|
Test
Report No. |
Customer
|
|
|
7M
3X25+1X25+1X16 - 640/1100 V |
AS PER NCB 188/1978
+ AMD. 5 |
E/T/7/2000
DT 23/5/2000 |
DONE AT CMRI
|
|
|
4X50
RR 1.1 kV |
AS PER IS 9968
PART I/1988 |
E/T/20/91
DT 7/11/91 |
DONE AT CMRI
|
|
|
RCgCR
3X120+3X70/3 6.35 kV |
AS PER IS 9968
PART II/1981 |
E/T/21/91
DT 7/11/91 |
DONE AT CMRI
|
|
|
RCgCESR
3X70+3X35/3 6.6 kV (UE) |
AS PER IS 9968
PART II/1981 |
E/T/7/92
DT 12/3/92 |
DONE AT CMRI
|
|
|
YWY
4X2.5 MM2 650/1100V MINIUM |
AS PER IS I554
PART I/1988 |
E/T/13/99
DT 25/10/97 |
|
|
|
KEMA
TEST
REPORT Back
To Top |
|
|
Cable
Type
|
Test
Details
|
Test
Report No. |
Customer
|
|
|
2XCY1x630
RM/V 127/220 kV |
AS PER IEC-840/1988
|
22192.00-HSC.
93-1078
DT 18/5/1993 |
KEMA, NETHE-
-RLAND |
|
|
BVIS
TEST
REPORT |
|
|
Cable
Type |
Test
Details |
Test
Report No.
|
Witnessed
by
|
|
|
A2XCEWY
3x95 6.35/11 kV |
AS PER BS-6622/1991
|
8/8/97
|
BVIS |
|
|
APLyYWY
4x95 600/1100 V |
AS PER BS-6480/1988
|
2/23/98
|
BVIS |
|
|
A2XFY
2x25 0.6/1 kV |
AS PER IEC 502/1994
|
8/8/97
|
BVIS |
|
|
2XCYWaY
1X500 18/30 kV |
AS PER IEC 502/1994
|
9/7/98
|
BVIS |
|
|
A2XCEWY
3x95 6/10 kV |
AS PER IEC 502/1994
|
8/8/97
|
BVIS |
|
|
ERDA
TEST
REPORT Back
To Top |
|
|
Cable
Type
|
Test
Details
|
Test
Report No. |
Customer
|
|
|
AYFY
3X400 1.1 kV |
Tests for UV
Exposure as per ASTM-4-53-1984 on outer sheath
|
1.02/11/1395
DT 28/3/95 |
|
|
|
A2XCEFY
11 kV |
Tests for UV
Exposure as per ASTM-4-53-1984 on outer sheath
|
1.02/11/1287
DT 7/4/93 |
|
|
|
A2XCEFY
3X185 11 kV |
Tests for UV
Exposure as per ASTM-4-53-1984 on outer sheath
|
1.02/11/951
DT 3/11/93 |
|
|
|
RITES
TEST
REPORT Back
To Top |
|
|
Cable
Type
|
Test
Details |
Test
Report No. |
Witnessed
by |
|
|
RR
1X25 -
1500 V |
E14/01 PART II
REV II-1993 |
5/19/00
|
RITES
|
|
|
RR
19X3 -
750 V |
E14/01 PART I
REV II-1993 |
3/28/00
|
RITES
|
|
|
RR
1X120 - 1500 V |
E14/01 PART II
REV II-1993 |
3/28/00
|
RITES
|
|
|
RR
1X270 - 1500 V |
E14/01 PART II
REV II-1993 |
3/28/00
|
RITES
|
|
|
RR
1X225 - 1500 V |
E14/01 PART II
REV II-1993 |
2/23/96
|
RITES
|
|
|
RR
1X2.5 -
750 V |
E14/01 PART I
REV II-1993 |
2/23/96
|
RITES
|
|
|
RR
1X120 - 1500 V |
E14/01 PART II
REV II-1993 |
2/17/95
|
RITES
|