For installation condition other than the standard ones
rating factors have to be applied as given in tables.
Arrangement for which reduction in current rating is not required:
For
cables sizes upto 70 sq. mm. conductor section, reduction
in rating for grouping for cable in air need not be
applied, provided, the circuits are run with a clearance
of at least 75 mm and installed in a horizontal plane,
when number of circuits are more than three. For cables
above 70 sq. mm. conductor section, no reduction in
rating be applied provided the circuits are run with
a clearance of at least 150 mm, and installed in a horizontal
plane as and when the number of circuits exceed four.
Short time and intermittent Rating
As in the case of any other electrical equipment, electric
cables also, although, designed to carry a continuous
load with a specified temperature rise under defined
ambient conditions; are capable of carrying loads in
excess of such continuous ratings for short duration
without harmful effect. If the cables are loaded cyclically,
having considerable no load or low load periods followed
by short overload periods, the current carrying capacity
is comparatively higher than the normal current rating.
However, this has to be worked out based on the actual
working conditions.
Back
to top
Cables exposed to Solar radiation:
To reduce the effect of solar radiation it is recommended
that the cable should be shielded from the direct rays
of the Sun without restricting the ventilation. On account
of hating of the exposed cable due to solar radiation
the rating of the cable installed out-doors and not
shielded from the Sun is less if shielded. It is advisable
to shield the exposed portion of the cable route from
the direct rays of Sun instead of using larger size
of cable for the entire route.
Bending
Radius:
While
installing TROPOTHEN-X Cable, the following minimum
bending radius should be observed, so that the cable
and especially the insulation is not damaged. Wherever
possible larger bending radii should be used.
| No.
of Cores |
Voltage
grade kV |
Min.
Bending Radius |
| Single
core |
Upto
11 kV (E) |
15
x D |
| Above
11 kV (E) |
20
x D |
| Multi
core |
Upto
1.1 kV (E) |
12
x D |
| Above
1.1 kV (E) |
15
x D |
|
Where
D is overall diameter of the cable